gas pressure switch heater,boiler, furnace

Gas Pressure Switch for Heater, Boiler, Furnace

Basic Info


Component: SemiConductor Type
Output Signal Type: Digital Type
Material: Metal
Wiring Type: Five-Wire
IP Rating: IP65
Contacts: Normally Open
Application: Industrial
Trademark: Bingo
Specification: PS-LA2
Type: Electronic
For: Strain Gauge Pressure Transmitter
Production Process: Normal Wirewound
Thread Type: ZG
Measuring Medium: Steam
Certification: CE
Explosion-Proof Type: Non Explosion-Proof
Medium: Air , Products of Combustion, or Natural Gas
Transport Package: Carton

Product Description


We are wholesaler, and exporter for Heater Pressure Switch PS-LA2 in China since 2009. Quick response, fast delivery.
Introduction:
Heater Pressure Switch PS-LA2 adopts a differential pressure to actuate a precision snap switch at chosen pressure setting. This may be the difference between atmospheric and a negative or positive pressure or between any two given pressures. When a change of pressure occurs between the negative pressure chamber and the positive pressure chamber the main diaphragm activates the snap switch at a pre-determined value.
It is manufactured from selected compound derivatives of polycarbonate & PBT offering exceptional thermal and dimensional stability at elevated temperatures up to 105º C when used in contaminated atmospheres of air, products of combustion, L. P. Or natural gas. It has been designed to meet the low pressure, high temperature specifications of future generations of fanned gas and similar appliances where differential pressures form part of an integral control systems.

Application


*Detects air flow in forced draught appliances
*Signals either positive, negative or zero air movement
*Shut down burner in blocked flue conditions
*Guards against poor or hazardous combustion
*Indicates dirty or inefficient filters
Technical Data:
Conversion: 1"W. C. = 1 inch/H2O=249PA 1mbar=100PA
MediumAir , products of combustion,  or natural gas
Mounting /Fixing4 screws with maximum penetration depth of 6.3mm into appropriate mounting holes, or fixed with optional bracket.
Mounting PositionIt can be mounted in most positions.
Field Adjustable Range0.4mbar ~ 8.0mbar (positive /negative pressure range). Minimum upper switching pressure 0.4mbar. Minimum lower switching pressure 0.2mbar.
Switch Differential≥0.1mbar, ≤0.3mbar, depending on pressure settings.
Max. Operating Pressure10mbar   Pmax=50mbar.
Operating Temperature Range≤105ºC
Electric Rating0.1A,3A,5A @125/250VAC. Other ratings are available on request.
Contact ArrangementSPDT / SPST
Terminals6.3 or 4.8 mm male Q.C. Optional insulation cover available as necessary.
CalibrationNormally calibrated at their lower switching pressure in accordance with customer requirements. Ramp rate at switch point=0.03mbar/second
Calibration ToleranceStandard production tolerance at ambient temperature is ± 0.10mbar or ± 5% of set point, whichever is the greater.
Connections6mm O.D. for tube connection
, , , , , , , , , , , , , , , , ,