Quick Details
Model Number: PS-LA11
Max. Current: 5A
Max. Voltage: 125V/250V
Max. Working Pressure: 800Pa
rated voltage: 125V/250V
rated current: 5A(0.5A)
Working pressure: 40Pa-800Pa
MAX temperature: 105℃
Medium: Air , products of combustion, L.P. or natural gas
Contact: SPDT,SPST-N.O.,SPST-N.C.
Connection: O.D.6.4mm
Color: Black
Size: 92X81X46mm
Introduction
PS-LA11 adopts a differential pressure to actuate a precision snap switch at chosen pressure setting. This may be the difference between atmospheric and a negative or positive pressure or between any two given pressures. When a change of pressure occurs between the negative pressure chamber and the positive pressure chamber the main diaphragm activates the snap switch at a pre-determined value.
It is manufactured from selected compound derivatives of polycarbonate & PBT offering exceptional thermal and dimensional stability at elevated temperatures up to 105°C when used in contaminated atmospheres of air, products of combustion, L.P. or natural gas. It has been designed to meet the low pressure, high temperature specifications of future generations of fanned gas and similar appliances where differential pressures form part of an integral control systems.
Technical Parameter
Media | Air , products of combustion, L.P. or natural gas |
Mounting /Fixing | 4 screws with maximum penetration depth of 6.3mm into appropriate mounting holes, or fixed with optional bracket. |
Mounting Position | The LFAS is position sensitive. It may be mounted in most positions provided it has been calibrated. |
Field Adjustable Range | 0.4mbar to 8.0mbar make on positive or negative pressure rise. Minimum upper switching pressure 0.4mbar. Minimum lower switching pressure 0.2mbar. |
Switch Differential | Not less than 0.1mb and not greater than 0.3mb depending on pressure settings. |
Maximum Operating Pressure | 10mbar Pmax=50mbar. |
Operating Temperature Range | 105°C Maximum |
Electric Rating | 125V,250V, 5A single pole on-off or single pole change over. Other ratings are available on request. |
Contact Arrangement | SPDT or SPST |
Terminals | 6.3 or 4.88 mm male Q.C. Optional insulation cover available as necessary. |
Calibration | LFAS switches are normally calibrated at their lower switching pressure in accordance with customer requirements. Ramp rate at switch point=0.03mb/second |
Calibration Tolerance | Standard production tolerance at ambient temperature is ± 0.10mb or ± 5% of set point, whichever is the greater. |
Pressure Connections | 6mm O.D. push on or "Permifix" tubing. The lower (negative) connector may be supplied in any one of four positions for ease of installation. |
Our Services
1. Delivery in time,delivery time is 7 days for sample and 15 working days for bulk order
2. Strong production capacity and strict quality control system;
3. Your inquiry and problems related to our products or prices will be replied in 24 hours;
4. Well-trained and experienced staffs to answer all your inquires;
5. After-sale tracking service for all of our clients;
6. OEM is available; small quantities, mixed bulk orders are also welcome;
7. Payment: L/C, D/A, D/P, T/T, Paypal , Western Union, MoneyGram;
8. Delivery way: UPS, DHL, TNT, FEDEX, EMS, CHINA POST.